Меню расширенной настройки, Страница 17, Продолжение) – Инструкция по эксплуатации Outback Power Systems FLEXpower ONE System Overview
Страница 17: Страница 2 страница 3 страница 4 страница 1
Инвертор
страница 17
ADV/FX/PAGE2--------P01
choose category
ADV GRID GEN PG3
ADV/FX/GRID---------P01
ac 1/grid 108
Vac lower limit
DOWN INC DEC PORT
ADV/FX/GRID---------P01
ac 1/grid 140 Vac
upper limit
DOWN INC DEC PORT
ADV/FX/GRID---------P01
ac 1/grid 48.0 Aac
input limit
DOWN INC DEC PORT
ADV/FX/GRID---------P01
ac 1/grid 6 cycles
transfer delay
DOWN INC DEC PORT
ADV/FX/GRID---------P01
grid programming
completed
TOP ADV MAIN
ADV/FX/GEN----------P01
gen input 00.5 min
connect delay
DOWN INC DEC PORT
ADV/FX/GEN----------P01
ac 2/gen 108 Vac
lower limit
DOWN INC DEC PORT
ADV/FX/GEN----------P01
ac 2/gen 140.0 Aac
upper limit
DOWN INC DEC PORT
ADV/FX/GEN----------P01
ac 2/gen 48.0 Aac
input limit
DOWN INC DEC PORT
ADV/FX/GEN----------P01
ac 2/gen ON
support
DOWN INC DEC PORT
ADV/FX/GEN----------P01
ac 2/gen 60
cycles transfer delay
DOWN INC DEC PORT
ADV/FX/GEN----------P01
gen programming
completed
TOP ADV MAIN
ADV/FX/PAGE4---------P01
choose category
PG3 SELL CAL MAIN
ADV/FX/SELL----------P01
sell re 23.6 Vdc
volts
DOWN INC DEC PORT
ADV/FX/SELL----------P01
grid tie IEEE
window
DOWN IEEE USER PORT
ADV/FX/SELL----------P01
selling
setup completed
TOP ADV MAIN
ADV/FX/SELL----------P01
grid tie GRIDTIE
authority
DOWN IEEE USER PORT
ADV/FX/AUX-----------P01
loadshed 22.0 Vdc
off set point
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
vent fan 26.0 Vdc
on set point
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
vent fan off 5 min
period
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
diversion 29.2 Vdc
on set point
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
diversion 30 sec
off delay
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
aux output
setup completed
TOP ADV MAIN
ADV/FX/PAGE3---------P01
choose category
PG2 AUX STACK PG4
ADV/FX/AUX-----------P01
aux output AUTO
control
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
aux output cool fan
function
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
genalert 22.0 Vdc
on setpoint
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
genalert 4 min
on delay
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
genalert 28.0 Vdc
off set point
DOWN INC DEC PORT
ADV/FX/AUX-----------P01
genalert 9 min
off delay
DOWN INC DEC PORT
ADV/FX/CALIBRATE-----P01
Vac input 120 vac
adjustment
DOWN INC DEC PORT
ADV/FX/CALIBRATE-----P01
Vac output 120 Vac
adjustment
DOWN INC DEC PORT
ADV/FX/CALIBRATE-----P01
calibration
setup completed
TOP ADV MAIN
ADV/FX/CALIBRATE-----P01
battery Vdc 25.4 Vdc
adjustment
DOWN INC DEC PORT
ADV/FX/PAGE1
choose category
ADV INV CHRG PG2
ADV/FX/STACK---------P01
stack 1-2PH Master
phase
DOWN INC DEC PORT
ADV/FX/STACK---------P01
stack Classic Slave
phase
DOWN INC DEC PORT
ADV/FX/STACK---------P01
stack OB Slave L1
phase
DOWN INC DEC PORT
ADV/FX/STACK---------P01
stack OB Slave L2
phase
DOWN INC DEC PORT
ADV/FX/STACK---------P01
stack 3PH Master
phase
DOWN INC DEC PORT
ADV/FX/STACK---------P01
stack 3 PH Slave
phase
DOWN INC DEC PORT
ADV/FX/STACK---------P01
power save level 0
master adjust only
DOWN INC DEC PORT
MAIN--------------------
3:02:14P
SUM STATUS SETUP ADV
ADV/FX/STACK---------P01
stacking
setup completed
TOP ADV MAIN
ADV/FX/STACK---------P01
power save level 0
slave adjust only
DOWN INC DEC PORT
Продолжение.
Начало см. на
предыдущей
странице.
страница 2
страница 3
страница 4
страница 1
Меню расширенной настройки
(продолжение)
Для возврата к главному
экрану в любое время:
Нажмите и удерживайте 2 левые программируемые клавиши
одновременно. Отпустите, когда появится главный экран.
MAIN-------------------
3:02:14P
SUM STATUS SETUP ADV
Экран главного меню
Примечание: значения, приведенные в данном
примере, могут варьироваться в зависимости от
модели инвертора.
900-0094-05-00 Rev A .vsd\INV Setup 2\2 марта 2012 г.
©2011 OutBack Power Technologies. Авторские права защищены.